003N0107 Danfoss Water Valve Temp controlled 1/2" AVTA15 2.3m Capillary 10C to 80C – Danfoss Water Valves AVTA/AVTB Ranges

Danfoss · SKU 003N010700 · Mfr no. 003N0107

003N0107 Danfoss Water Valve Temp controlled 1/2" AVTA15 2.3m Capillary 10C to 80C

The 003N0107 Danfoss Water Valve Temp controlled 1/2" AVTA15 2.3m Capillary 10C to 80C is supplied by Air Conditioning Installation as part of the Danfoss Danfoss Water Valves AVTA/AVTB Ranges range. It is listed under manufacturer part number 003N0107 and our product code 003N010700. Key details: capillary: 90 9/16 in;2300 mm; charge type: Adsorption; type: AVTA 15. You can buy it as a unit-only supply, or have our engineers fit it as part of a full installation or service visit. Call 07414 254125 to check stock, get a price or book fitting.

Call for price

BrandDanfoss
Manufacturer Part Number003N0107
Product Code003N010700
Capillary90 9/16 in;2300 mm
Charge TypeAdsorption
TypeAVTA 15
Product GroupDanfoss Water Valves AVTA/AVTB Ranges
FamilyAVTA
Capillary Tube GlandInternal
Capillary Tube Gland Size1/2 in
Capillary Tube Gland TypeG
Connection Internal/ExternalInternal
Connection Size1/2 in
Connection TypeG
Kv Value1.900 m³/h
Commodity Code84818059
Country Of OriginPOL
EAN5702423015559
Gross Weight1.55 kg
Body MaterialBrass
Capillary Tube Length2,300 mm
Weight1.27 kg
Diff Pressure Range0.0-10.0 Bar
Max Operating Pressure16.0 Bar
Sensor Size (Diameter x Length)3/8x529/32 in
ApprovalEAC
Max Sensor Temperature130 °C
Medium Temperature Range-25-130 °C
Temperature Range10-80 °C
CV Value2.200 gal/min
Flow Direction IndicatorEmbossed 1-way arrow
MediaNeutral media
Opening ConfigurationOpens on rising sensor temp.
Orifice Size15.00 mm;3/5 in
F-Gas Certificate RequiredNo

WVFX, WVO and WVS pressure operated water valves are used to regulate the flow of water in refrigeration plant with watercooled condensers in order to ensure constant proportional regulation of condensing pressure. The water valve modulates the water flow to maintain the condensing pressure at a constant level during operation. When the refrigeration plant is stopped, the cooling water flow is shut off automatically. Media: fresh water and neutral brine. For use with aggressive media such as sea water, WVFX 15, WVFX 20 and WVFX 25 are available in stainless steel versions.

Frequently asked questions

What is the manufacturer part number for the Danfoss Water Valve Temp controlled 1/2" AVTA15 2.3m Capillary 10C to 80C?

The manufacturer part number is 003N0107 (Danfoss). Our product code is 003N010700. Quote either when you call 07414 254125.

Which range does the 003N0107 belong to?

It belongs to the Danfoss Water Valves AVTA/AVTB Ranges range from Danfoss. See the full specification table on this page for technical details.

Does the 003N0107 need an F-Gas certified engineer?

The supplier does not flag an F-Gas certificate requirement for this item on its own. If it forms part of a refrigerant system, the system work must still be carried out by an F-Gas registered engineer, which all of ours are.

Can you supply and install the 003N0107?

Yes. You can order the unit only, or book supply and professional installation by our F-Gas certified engineers. Call 07414 254125 or use the booking button on this page.

How much is the 003N0107?

Prices change with stock and trade pricing, so call 07414 254125 for today's price, with or without installation.